A current deviation control parameter tuning method to suppress subsequent commutation failure
Author:
Affiliation:

Clc Number:

TM721

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    If a subsequent commutation failure occurs in the line commutated converter-based high voltage direct current (LCC-HVDC) transmission system,it will have a seriously negative impact on the safe and stable operation of the AC-DC hybrid power grid. Aiming at the problem of commutation failure during the current deviation control stage in the fault recovery process of the LCC-HVDC system,the relationship between current deviation control parameter and commutation failure is analyzed theoretically. It is found that to avoid commutation failure at this stage,the DC voltage and AC commutation voltage at the inverter side of the LCC need to meet certain constraints. These constraints are directly affected by the current deviation control parameter. Based on the theoretical analysis results,a current deviation control parameter tuning method is proposed,which can improve the control requirements for DC voltage recovery speed and degree during the fault recovery process of the system. The method makes it easier for the system to meet the stable operation constraints between DC voltage and AC commutation voltage,thereby reducing the probability of subsequent commutation failure. Finally,the CIGRE standard test model in the PSCAD/EMTDC simulation platform is used to verify the correctness of the theoretical analysis and the effectiveness of the parameter tuning method.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:February 21,2024
  • Revised:May 05,2024
  • Adopted:December 06,2023
  • Online: July 23,2024
  • Published: July 28,2024