Partial damp diagnostic method of oil-paper insulating bushing based on frequency domain spectroscopy
Author:
Affiliation:

Clc Number:

TM732

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Partial dampness is the initial stage in the bushing damp process,so the effective diagnosis of partial dampness can avoid the further development of the damp. The partial damp diagnosis method of bushing based on the frequency domain spectroscopy (FDS) is proposed in this paper. Firstly,oil-paper insulation samples with different moisture content are prepared,and partial damped samples are formed through combination. Then the FDS characteristics are obtained. The results show that partial distribution of moisture leads to oil-paper insulation interfaces with different moisture content,and the interface relaxation polarization loss peak is introduced in the FDS curves. The greater the degree of partial dampness in the radial direction,the greater the amplitude of the loss peak,and it moves to the high frequency direction. The effectiveness of the diagnosis of partial dampness of bushing based on the characteristics of the interface relaxation polarization loss peak is verified by the simulation model of the transformer bushing. It shows that a new method for early fault warning and diagnosis of the transformer bushing is provided.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:October 23,2021
  • Revised:December 27,2021
  • Adopted:June 11,2021
  • Online: March 24,2022
  • Published: March 28,2022
Article QR Code