Optimization of voltage differential protection for UHVDC transmission line
Author:
Affiliation:

Clc Number:

TM721.1

Fund Project:

National Key R&D Program of China(No.2016YFB0900600;Technology Projects of State Grid Corporation of China(No.52094017000W)

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Ground fault tests of ultra-high voltage direct current (UHVDC) transmission line indicate that voltage differential protection of the other pole may be false tripped when the ground fault happens on the line of the pole with a larger number of operating valve groups. In order to solve this problem,it is pointed out that the transmission velocity of common-mode of the fault traveling wave is less than that of differential-mode,and there is a time difference between common-mode and differential-mode to reach the protection measurements. Then,it is analyzed that the cause of the voltage differential protection false tripping is that the time difference between common-mode and differential-mode to reach the protection measurements is longer than the setting time of the protection. In addition,the polarity of common-mode component is used as the criterion to identify the fault pole and the protection of voltage mutation is improved accordingly. Finally,a real-time digital simulation model of UHVDC transmission is established to verify the correctness of the analysis results for the impoved method.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:January 06,2022
  • Revised:March 12,2022
  • Adopted:February 09,2022
  • Online: May 24,2022
  • Published: May 28,2022
Article QR Code