Analysis of PROFIBUS DP Alarm in Xizhe HVDC Project
Author:
Affiliation:

Clc Number:

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    In Xizhe HVDC project the PROFIBUS DP communication false alarm occurs frequently,which is triggered by the detection of the heartbeat signal.It is found that the PROFIBUS DP communication system is a multi-link asynchronous system.The time window of the heartbeat signal is changed by the data transfer in the multi-link asynchronous system,and the continuous multi-frame has the same heartbeat signal,which causes the false alarm of PROFIBUS DP.In this paper,the characteristics of heartbeat signal transmission in multi-link asynchronous system are analyzed in detail.The research method can be applied to similar structure commnunication systems.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:October 08,2016
  • Revised:December 21,2016
  • Adopted:March 09,2017
  • Online: May 27,2017
  • Published: