基于振动非线性特征的变压器绕组状态检测
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM41

基金项目:

浙江省自然科学基金资助项目(LY22F030001)


Transformer winding condition detection based on the nonlinear characteristics of vibrations
Author:
Affiliation:

Fund Project:

Natural Science Foundation of Zhejiang Province

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    电力变压器是电网系统中的关键设备,绕组又是变压器的核心部件。为了对带电绕组进行状态检测,文中根据绕组结构参数随负载变化的关系,建立振动幅值与电流之间的非线性模型,证明了结构刚度与模型参数的数值关系,并提出基于振动非线性特征的绕组压紧力评价方法。实验中,在调整绕组轴向压紧力的同时进行短路负载实验,获取电流与振动幅值的关系,结果表明,在绕组压紧力较小的情况下,振动的非线性特征较显著,且特征参数C3准确反映了绕组结构等效刚度的变化。在实际应用中,比较正常绕组和松动绕组对应的油箱表面振动特征,并将结果以二维等高线的形式呈现,结果表明,油箱表面振动特征体现了测点附近绕组的结构状态。上述结果证明特征参数C3是压紧力的单调函数,当该数值大于0.5时绕组存在结构状态劣化。

    Abstract:

    Power transformers are critical devices in power grid systems,with windings as their core components. To perform state detection on online windings,this paper establishes a nonlinear model between vibration amplitude and current based on the relationship between winding structural parameters and load variations. The numerical relationship between structural stiffness and model parameters is proved,and a winding clamping force evaluation method based on the nonlinear characteristics of vibrations is proposed. In the experiment,the relationship between current and vibration amplitude is obtained by adjusting the axial clamping force of windings and performing short-circuit load tests. The experimental results show that the nonlinear characteristics of vibrations are significant when the winding clamping force is small,and the characteristic parameter C3 accurately reflects the equivalent stiffness change of the winding structure. In practical applications,the vibration characteristics of oil tank surface corresponding to normal windings and loose windings are compared,and the results are presented in the form of two-dimensional contour plot. The results indicate that the vibration characteristics of the tank reflect the structural state of the winding near the measurement point. The above results demonstrate that the parameter C3 is a monotonic function of clamping force,and there is structural degradation in the winding when this value is greater than 0.5.

    参考文献
    相似文献
    引证文献
引用本文

钱国超,胡锦,代维菊,王浩州,赵汉武,洪凯星.基于振动非线性特征的变压器绕组状态检测[J].电力工程技术,2024,43(6):194-202

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2024-04-07
  • 最后修改日期:2024-06-15
  • 录用日期:2024-04-15
  • 在线发布日期: 2024-11-26
  • 出版日期: 2024-11-28
文章二维码