基于测量电压弗雷歇距离的柔性直流配电线路保护
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM77

基金项目:

国家自然科学基金资助项目(52277170)


Flexible DC distribution line protection based on measuring voltage Fréchet distance
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    多端柔性直流配电系统发展迅速,在新能源接入方面有明显优势,但故障的快速、可靠识别是其发展面临的难点之一。针对多端柔性直流配电线路高阻故障特征不明显、保护难以识别的问题,文中通过分析换流站闭锁前的暂态电压故障特性,提出一种基于测量电压弗雷歇距离的柔性直流配电线路单端量保护方案。首先,基于正、负极测量电压和电流暂态变化率构造保护启动判据;其次,通过正、负极测量电压变化率区分单、双极故障;最后,利用单、双极测量电压弗雷歇距离构造积分识别单、双极区内外故障,并根据正极测量电压变化率对单极故障进行选极。经PSCAD/EMTDC仿真结果表明,此方案能同时满足保护对速动性和灵敏性的要求,且具备良好的耐过渡电阻能力,不受线路分布电容的影响。

    Abstract:

    The multi-terminal flexible DC distribution system has developed rapidly and has obvious advantages in integrating new energy. However,rapid and reliable fault identification is one of the challenges in its development. To address the issue of the inconspicuous high-resistance fault characteristics of multi-terminal flexible DC distribution lines and the associated protection difficulties,this paper proposes a single-ended protection scheme for flexible DC distribution lines based on measuring voltage Fréchet distance by analyzing the transient voltage fault characteristics before the converter station blocking. Firstly,the protection start-up criterion is constructed based on the transient change rates of voltage and current measured by the positive and negative electrodes. Secondly,single-pole and bipolar faults are distinguished by the voltage change rate measured by the positive and negative electrodes. Finally,the internal and external faults in the unipolar and bipolar regions are identified by using the single and bipolar measurement voltage Fréchet distance to construct the integral,and the unipolar fault is selected according to the positive electrode voltage change rate. The PSCAD/EMTDC simulation results show that this scheme can simultaneously meet the requirements for rapidity and sensitivity in protection,and has good resistance to transition resistance,which is not affected by the distributed capacitance of the line.

    参考文献
    相似文献
    引证文献
引用本文

金恩淑,张双双,胡晓晨,王汝田.基于测量电压弗雷歇距离的柔性直流配电线路保护[J].电力工程技术,2024,43(6):142-152,182

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2024-04-04
  • 最后修改日期:2024-06-11
  • 录用日期:2023-12-12
  • 在线发布日期: 2024-11-26
  • 出版日期: 2024-11-28
文章二维码