提升双馈风力发电系统低电压穿越能力的跟踪控制方法
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM614

基金项目:

国家自然科学基金资助项目(51707147);陕西省重点研发计划重点产业创新链资助项目(2017ZDCXL-GY-02-03)


A tracking control method for doubly-fed induction generator to enhance the low voltage ride through capability
Author:
Affiliation:

Fund Project:

National Natural Science Foundation of China (51707147);Key Research and Development Program of Shaanxi (2017ZDCXL-GY-02-03);State Grid Shaanxi Electric Power Company Science and Technology Project (B626KY190005)

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为提升双馈风力发电系统的低电压穿越(LVRT)能力,提出一种基于状态相关Riccati方程(SDRE)技术的网侧换流器(GSC)跟踪控制方法。并网导则要求风电场在LVRT过程中须注入一定无功功率支撑电压恢复,为了改进非线性状态调节器在无功支撑能力上的不足,针对双馈风力发电系统的GSC设计非线性无功功率跟踪控制器,并采用SDRE技术求解状态反馈控制律。在维持LVRT过程中直流电压稳定的基础上,该方法能充分利用GSC的无功功率调节能力,为电网提供无功功率支撑以避免电压恶化。最后,在Matlab/Simulink平台搭建9 MW双馈风力发电系统,并在三相接地故障下进行仿真验证,结果显示,所提出的GSC控制方法具有良好的暂态表现,能够有效提高双馈风力发电系统的LVRT能力。

    Abstract:

    In order to improve the low voltage ride through (LVRT) capability of doubly-fed induction generator (DFIG), a tracking control method for grid side converter (GSC) based on state-dependent Riccati equation (SDRE) technique is proposed. The grid code requires that wind farms should inject reactive power to support voltage recovery during LVRT process. In order to improve the supporting capacity of the nonlinear state-regulator on reactive power, nonlinear reactive power tracking controller is designed in GSC of DFIG, and the state feedback control law is obtained through solving state dependent Riccati equation. On the basis of maintaining the stability of DC link voltage in LVRT process, the reactive power regulation capability of GSC is fully utilized to provide reactive power support for the power grid to avoid voltage deterioration. Finally, a 9 MW DFIG-based wind farm is built by Matlab/Simulink. The simulation results show that the proposed GSC control method has good transient performance and effectively improves the LVRT capability of DFIG through simulation verification under three phase ground faults.

    参考文献
    相似文献
    引证文献
引用本文

王若谷,张若微,王明杰,高欣,秦博宇.提升双馈风力发电系统低电压穿越能力的跟踪控制方法[J].电力工程技术,2021,40(2):185-191

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2020-09-14
  • 最后修改日期:2020-10-26
  • 录用日期:2020-11-09
  • 在线发布日期: 2021-04-02
  • 出版日期: 2021-03-28
文章二维码