基于改进MCCIPM的含TCPST电力系统最优潮流计算
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

TM744

基金项目:

国家重点研发计划资助项目(2018YFB0904500);江苏省"333高层次人才培养工程"专项资助项目(BRA2020084)


Optimal power flow calculation of power system containing TCPST based on improved MCCIPM
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    随着可控移相器(TCPST)在现代电力系统中应用水平的逐渐提高,计及TCPST的系统最优潮流(OPF)计算迎来了新的挑战。文中提出了一种基于改进内点法的含TCPST电力系统OPF计算方法。首先,结合TCPST接入系统的等效功率注入模型,以系统有功网损最小为目标建立含TCPST的最优潮流模型;其次,为提高收敛速度,文中针对多中心-校正内点法(MCCIPM)进行改进,提高了仿射方向迭代步长并重新配置关键映射参数;最后,基于改进后的MCCIPM,在IEEE 14、IEEE 30和IEEE 118节点网络完成OPF计算。测试结果表明,TCPST具有控制线路潮流分布的能力,验证了文中计算方法在求解效率上的优越性。

    Abstract:

    As more and more flexible AC transmission devices are used in modern power systems,the research of optimal power flow (OPF) with thyristor controlled phase shifting transformer (TCPST) is facing new challenges. In order to ensure the security of the system,the equivalent power injection model of the TCPST access system is combined to establish the optimal power flow model with TCPST with the objective function of the minimum active power loss. In order to improve the convergence speed,the multicenter correction interior point method is improved. The iteration step of the affine direction is improved and the key mapping parameters is reconfigured. Based on the improved multicenter correction interior point method,the optimal power flow calculation test is completed in IEEE 14,IEEE 30 and IEEE 118 node networks,and the control ability of TCPST to line power flow distribution is tested. The test results show that the improved interior point method proposed in this paper is feasible and practical.

    参考文献
    相似文献
    引证文献
引用本文

张宁宇,张恪,李群,刘建坤,赵静波,孙国强.基于改进MCCIPM的含TCPST电力系统最优潮流计算[J].电力工程技术,2021,40(5):144-150

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2021-03-21
  • 最后修改日期:2021-05-29
  • 录用日期:2020-10-19
  • 在线发布日期: 2021-09-30
  • 出版日期: 2021-09-28
文章二维码