电力系统频率响应的改进模型与参数估计
作者:
中图分类号:

TM744

基金项目:

国家自然科学基金资助项目(51837004);高等学校学科创新引智计划(111计划)资助项目“新能源发电与智能电网学科创新引智基地”(B14022)


The improved model and parameter estimation for frequency response of power system
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [27]
  • |
  • 相似文献 [20]
  • | | |
  • 文章评论
    摘要:

    近年来,多种因素导致电力系统频率大波动事故时有发生。而目前对电力系统调频能力预估误差较大,有必要采用电力系统频率响应(SFR)模型计算频率的动态响应。文中分析了SFR经典模型的不足之处,据此改进了SFR模型结构,其中考虑了等值调速器的动态特性。进而提出了SFR改进模型的参数估计方法,先直接计算获得部分参数,然后加入保证稳态一致性的参数约束条件,最后辨识获得其余参数。通过仿真算例对频率响应进行了计算,验证了SFR改进模型结构与参数估计方法的有效性。结果表明,SFR改进模型能够有效表征系统频率响应的主要指标,其精度显著高于SFR经典模型。

    Abstract:

    In recent years, many factors lead to the frequency fluctuation accident of power system occurring often. The simulation results of multiple faults show that the estimation error of frequency modulation capability of power system is large at present, so it is necessary to use the power system frequency response (SFR) model to calculate dynamic frequency response. The shortcomings of the classical SFR model are analyzed, and the structure of the SFR model is improved accordingly, in which the dynamic characteristics of the polymer governor are taken into account. Then a parameter tuning method for the improved SFR model is proposed. In this method some parameters are obtained by direct calculation, the parameter equation for keeping steady-state compliance is added, and the other parameters are identified. The structure and parameters of the model are calculated in the simulation example, which verifies the validity of the improved SFR model and parameter tuning. The results indicate that the improved SFR model represent the major characteristics of SFR very well, and its accuracy is much higher than the classical SFR model.

    参考文献
    [1] 张恒旭,李常刚,刘玉田,等. 电力系统动态频率分析与应用研究综述[J]. 电工技术学报,2010,25(11):169-176. ZHANG Hengxu,LI Changgang,LIU Yutian,et al. Reviews on power system dynamic frequency analysis and its application[J].Transactions of China Electrotechnical Society,2010,25(11):169-176.
    [2] 曾嘉俊, 黄健洪, 郝旭东. 基于状态反馈线性化的电力系统动态频率控制[J]. 智慧电力, 2017, 45(9):40-44. ZENG Jiajun, HUANG Jianhong, HAO Xudong. Dynamic frequency control of power systems based on statefeedback linearization[J]. Smart Power, 2017, 45(9):40-44.
    [3] 吴云亮, 肖峥, 闫秉科, 等. 微电网协调频率和电压控制策略研究[J]. 陕西电力, 2017, 45(2):15-20. WU Yunliang, XIAO Zheng, YAN Bingke, et al. Coordinated frequency and voltage control strategy for microgrid[J]. Shaanxi Electric Power, 2017, 45(2):15-20.
    [4] 任佳. 区域电网安全稳定控制系统策略制定探讨[J]. 电工技术,2016(10):13-15. RENG Jia. Discussion on strategy formulation of regional power grid security and stability control system[J]. Electric Engineering,2016(10):13-15.
    [5] 李卫东,晋萃萃,温可瑞,等. 大功率缺失下主动频率响应控制初探[J]. 电力系统自动化,2018,42(8): 22-30. LI Weidong,JIN Cuicui,WEN Kerui,et al. Active frequency response control under high-power loss[J]. Automation of Electric Power Systems,2018,42(8):22-20.
    [6] 董希建, 罗剑波, 李雪明, 等. 交直流混联受端电网频率紧急协调控制技术及应用[J]. 电力系统保护与控制, 2018, 46(18):59-66. DONG Xijian, LUO Jianbo, LI Xueming, et al. Research and application of frequency emergency coordination and control technology in hybrid AC/DC power grids[J]. Power System Protection and Control, 2018, 46(18):59-66.
    [7] 邓晖,楼伯良,华文,等. 基于直流闭锁事故的华东电网频率特性及控制措施[J]. 广东电力,2018,31(2):76-81. DENG Hui, LOU Boliang, HUA Wen, et al. Frequency characteristic of east china power grid based on DC block accidents and control measures[J]. Guangdong Electric Power,2018,31(2):76-81.
    [8] 齐旭,曾德文,史大军,等. 特高压直流输电对系统安全稳定影响研究[J]. 电网技术,2006(2):1-6. QI Xu,ZENG Dewen,SHI Dajun,et al. Study on impacts of UHVDC transmission on power system stability[J]. Power System Technology,2006(2):1-6.
    [9] 鲁宗相,汤海雁,乔颖,等. 电力电子接口对电力系统频率控制的影响综述[J]. 中国电力,2018,51(1):51-58. LU Zongxiang,TANG Haiyan,QIAO Yin,et al. The impact of power electronics interfaces on power system frequency control:a review[J]. Electric Power,2018,51(1):51-58.
    [10] 覃琴,郭强,周勤勇,等. 国网“十三五”规划电网面临的安全稳定问题及对策[J]. 中国电力,2015,48(1): 25-32. QIN Qin,GUO Qiang,ZHOU Qinyong,et al. The security and stability of power grids in 13th five-year planning and countermeasures[J]. Electric Power,2015,48(1):25-32.
    [11] 李国栋,皮俊波,郑力,等. ±500 kV林枫直流双极闭锁故障案例仿真分析[J]. 电网技术,2014,38(4): 877-881. LI Guodong,PI Junbo,ZHENG Li,et al. Simulation analysis on case of bipolar blocking in ±500 kV EHVDC power transmission line from Tuanlin to Fengjing[J]. Power System Technology,2014,38(4):877-881.
    [12] 邓晖,楼伯良,华文,等. 特高压直流闭锁后华东电网频率稳定特性研究[J]. 智慧电力,2017,45(8): 39-44. DENG Hun,LOU Boliang,HUA Wen,et al. frequency stability analysis of east china power grid due to HVDC block[J]. Smart Power,2017,45(8):39-44.
    [13] 付超,张丹,柳勇军,等. 含大规模直流送端电网的频率响应特性仿真分析[J]. 广东电力,2018,31(9):26-31. FU Chao, ZHANG Dan, LIU Yongjun, et al. Simulation analysis on frequency response characteristic of sending-end power grid with large-scale HVDC[J]. Guangdong Electric Power,2018,31(9):26-31.
    [14] 刘世凯, 赵健, 宋晨光, 等. 特高压直流系统单极闭锁外特性建模及仿真研究[J]. 陕西电力, 2017, 45(2):59-64. LIU Shikai, ZHAO Jian, SONG Chenguang, etal. Externalcharacteristic modeling of uhvdc unipolar blocking and simulation[J]. Shaanxi Electric Power, 2017, 45(2):59-64.
    [15] 华文,黄晓明,楼伯良,等. 宾金直流单极闭锁事故再现仿真分析[J]. 浙江电力,2016,35(2):7-10. HUA Wen,HUA Xiaoming,LOU Boliang,et al. reconstruction and simulation analysis of unipolar block in Yibin-Jinhua UHVDC power transmission project[J]. Zhejiang Power,2016, 35(2):7-10.
    [16] 李兆伟,吴雪莲,庄侃沁,等. “9·19”锦苏直流双极闭锁事故华东电网频率特性分析及思考[J]. 电力系统自动化,2017,41(7):149-155. LI Zhaowei,WU Xuelian,ZHUANG Kanqin,et al. Analysis and reflection on frequency characteristics of east china grid after bipolar locking of "9·19" Jinping-Sunan DC transmission line[J]. Automation of Electric Power Systems,2017,41(7):149-155.
    [17] 高强. ±800 kV宾金直流双极闭锁故障对浙江电网的影响[J]. 电网与清洁能源,2014,30(11):47-51. GAO Qiang. Impact of ±800 kV Yibin-Jinhua DC bipolar block fault on Zhejiang power grid[J]. Advances of Power System & Hydroelectric Engineering,2014,30(11):47-51.
    [18] 于昌海,吴继平,杨海晶,等. 规模化储能系统参与电网调频的控制策略研究[J]. 电力工程技术, 2019, 38(4):68-73. YU Changhai,WU Jiping,YANG Haijing,et al. Frequency regulation strategy for power grid incorprating large-scale energy storage[J]. Electric Power Engineering Technology,2019, 38(4):68-73.
    [19] 李虎成,袁宇波,卞正达,等. 面向特高压交直流大受端电网的频率紧急控制特性分析[J]. 电力工程技术, 2017, 36 (2):33-37. LI Hucheng,YUAN Yubo,BIAN Zhengda,et al. The frequency emergency control characteristic analysis for UHV AC/DC large receiving end power grid[J]. Jiangsu Electrical Engineering,2017, 36(2):33-37.
    [20] 薄其滨,王晓茹,刘克天. 基于v-SVR的电力系统扰动后最低频率预测[J]. 电力自动化设备,2015,35(7):83-88. BO Qibin,WANG Xiaoru,LIU Ketian. Minimum frequency prediction based on v-SVR for post-disturbance power system[J]. Electric Power Automation Equipment,2015,35(7):83-88.
    [21] 胡益,王晓茹,艾鹏,等. 基于广域量测的交直流混联系统发生扰动后稳态频率预测算法[J]. 电力自动化设备,2018,38(11):35-42. HU Yi,WANG Xiaoru,AI Peng,et al. Prediction algorithm of steady-state frequency after disturbance for hybrid AC/DC power system based on wide area measurement[J]. Electric Power Automation Equipment,2018,38(11):35-42.
    [22] 艾鹏,滕予非,王晓茹,等. 计及紧急直流功率支援的扰动后稳态频率预测算法[J]. 电力系统自动化,2017,41(13):92-99. AI Peng,TENG Yufei,WANG Xiaoru,et al. Prediction algorithm of steady frequency after disturbances considering emergency DC power support[J]. Automation of Electric Power Systems,2017,41(13):92-99.
    [23] CHAN M L,DUNLOP R D,SCHWEPPE F. Dynamic equivalents for average system frequency behavior following major distribances[J]. IEEE Transactions on Power Apparatus & Systems,1972, 91(4):1637-1642.
    [24] ANDERSON P M,MIRHEYDAR M. A low-order system frequency response model[J]. IEEE Transactions on Power Systems,1990,5(3):720-729.
    [25] 鞠平.现代电力系统控制与辨识[M]. 北京:清华大学出版社,2015. JU Ping.Modern power system control and identification[M]. Beijing:Tsinghua University Press,2015.
    [26] 王晓伟, 蒋平, 高磊, 等. 江苏电网电力系统稳定器参数辨识研究[J]. 江苏电机工程, 2007,26(2):13-15. WANG Xiaowei,JIANG Ping,GAO Lei,et al. Parameter identification of power system stabilizer in Jiangsu power grid[J]. Jiangsu Electrical Engineering, 2007, 26(2):13-15.
    [27] 倪以信,陈寿孙,张宝霖.动态电力系统的理论和分析[M]. 北京:清华大学出版社,2002. NI Yixin,CHEN Shousun,ZHANG Baolin.Theory and analysis of dynamic power system[M]. Beijing:Tsinghua University Press,2002.
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

李东辉,臧晓明,鞠平,陈谦.电力系统频率响应的改进模型与参数估计[J].电力工程技术,2019,38(5):85-90

复制
分享
文章指标
  • 点击次数:1879
  • 下载次数: 2519
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 收稿日期:2019-06-27
  • 最后修改日期:2019-08-05
  • 录用日期:2019-09-10
  • 在线发布日期: 2019-09-30
  • 出版日期: 2019-09-28
文章二维码