作者:

Improved Setting Method of Distance Protection for Transmission Line With Series Reactor
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [15]
  • |
  • 相似文献 [20]
  • | | |
  • 文章评论
    摘要:

    串联电抗器可以很好地限制电网的短路电流,但同时给输电线路继电保护带来了挑战。文中提出了一种带串联电抗器的输电线路距离保护整定改进方法,根据串联电抗器阻抗和线路阻抗重新整定零序电流补偿系数,根据串联电抗器阻抗和原距离保护阻抗定值重新计算距离保护定值。只需修改保护装置定值,无需改变距离保护算法代码,即可保证带串联电抗器的输电线路距离保护Ⅰ段的可靠性和距离保护Ⅱ段、Ⅲ段的灵敏性。仿真结果验证了文中方法在保护可靠性和灵敏性方面的效果。

    Abstract:

    The series reactor can limit the short circuit current of the power grid,but it also brings challenges to the relay protection.An improved setting method for the distance protection of transmission lines with series reactor is presented.The compensation coefficient of zero sequence current is adjusted according to the series reactor's impedance and line's impedance.The distance protection settings are calculated according to the series reactor's impedance and the original distance protection impedance.The improved setting method can guarantees the reliability and sensitivity of distance protection just by modifying the settings and without changing the code.The simulation results demonstrate the effectiveness of this method.

    参考文献
    [1] 贾磊,蔡汉生,胡上茂,等. 500 kV串联电抗器对线路断路器开断能力的影响研究[J].南方电网技术,2014,8(6):7-11. JIA Lei,CAI Hansheng,HU Shangmao,et al. Study on influence of 500 kV series reactor on interrupting capability of line circuit breaker[J]. Southern power system technology,2014,8(6):7-11.
    [2] 曾琦,李兴源,蔡鑫贵,等.带串联补偿故障限流器的仿真和实验[J].电力系统自动化,2003,27(14):54-56. ZENG Qi,LI Xingyuan,CAI Xingui,et al. Simulation and test of fault current limiter with series compensation[J]. Automation of Electric Power Systems,2003,27(14):54-56.
    [3] 徐宁,王莹,许文超,等.高压串联电抗器在南京220kV电网中的应用分析[J].江苏电机工程,2015,34(5):34-36. XU Ning,WANG Ying,XU Wenchao,et al. Analysis of the performance of high voltage series reactor in Nanjing 220kV-power-grid[J]. Jiangsu Electrical Engineering,2015,34(5):34-36.
    [4] 夏毅,刘建明.超导限流器对电力系统继电保护和暂态稳定的影响[J].电工电能新技术,2007,26(2):45-48. XIA Yi,LIU Jianming. Effect of superconducting fault current limiters on power system protection and transient stability[J]. Advanced Technology of Electrical Engineering and Energy,2007,26(2):45-48.
    [5] 刘宾.超导故障限流器及其对电力系统继电保护的影响研究[D].南京:东南大学,2013. LIU Bin. Research on SFCL and its effects on relay protection of power system[D]. Nanjing:Southeast University,2013.
    [6] 刘华蕾,江道灼,陈刚,等.安装固态短路限流器后距离保护整定的改进方法[J].电力系统自动化,2006,30(2):90-95. LIU Hualei,JIANG Daozhuo,CHEN Gang,et al. Improved setting method of distance protection with the SSFCL[J]. Automation of Electric Power Systems,2006,30(2):90-95.
    [7] SHAWN H,THOMAS B,MICHAEL S. The effects of fast switching fault current limiter on distance protection[C]//Procee-dings of the 35th Southeastern Symposium on System Theory,2003:264-268.
    [8] 金雪芬,戴朝波,武守远,等.故障电流限制器对继电保护的影响[J].电网技术,2010,34(6):98-105. JIN Xuefen,DAI Chaobo,WU Shouyuan,et al. Influence on fault current limiter on protective relaying[J]. Power System Technology,2010,34(6):98-105.
    [9] 魏繁荣,李慧,林湘宁,等.考虑TCSC型故障限流器动态过程的距离保护整定方法[J].中国电机工程学报,2017,37(8):2279-2289. WEI Fanrong,LI Hui,LIN Xianglin,et al. Distance protection setting strategy considering the dynamic impedance process of TCSC-FCL[J]. Proceedings of the CSEE,2017,37(8):2279-2289.
    [10] 潘磊,李斌,杨光,等.统一潮流控制器在交流系统故障时的处理策略研究[J].电力工程技术,2017,36(6):132-137. PAN Lei,LI Bin,YANG Guang,et al. Control and protection strategies of unified power flow controller during AC system failure[J]. Electric Power Engineering Technology,2017,36(6):132-137.
    [11] 沈军,张洪喜,王忠,等.一起距离保护误动事例分析以及解决方案[J].电力工程技术,2017,36(2):47-52. SHEN Jun,ZHANG Hongxi,WANG Zhong,et al. Analysis of a case of distance protection mal-operation and solution[J]. Electric Power Engineering Technology,2017,36(2):47-52.
    [12] 冯勇鑫,温渤婴.接地距离保护中零序补偿系数整定方法的探讨[J].电力系统及其自动化学报,2008,20(3):95-98. FENG Yongxin,WEN Boyin. Investigation on setting method for zero-sequence current compensation coefficient in ground-fault distance protection[J]. Proceedings of the CSU-EPSA,2008,20(3):95-98.
    [13] 王广学.电力系统接地距离保护零序补偿系数分析[J].电网技术,1994,18(1):1-7. WANG Guangxue. Analysis of zero-sequence current compensation coefficient for ground-fault distance protection in power system[J]. Power System Technology,1994,18(1):1-7.
    [14] 张保会,尹项根.电力系统继电保护[M].北京:中国电力出版社,2005. ZHANG Baohui,YIN Xianggen.Power system protective relaying[M]. Beijing:China Electric Power Press.
    [15] 刘宾,梅军,郑建勇,等.超导故障限流器接入电网后单相接地短路距离保护整定的改进措施[J].华东电力,2012,40(5):793-797. LIU Bin,MEI Jun,ZHEN Jianyong,et al. Improved distance protection setting method for the single-phase ground fault with grid-connected SFCL[J]. East China Electric Power,2012,40(5):793-797.
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

朱晓彤,陆金凤,谢华,赵青春,王忠.带串联电抗器输电线路距离保护整定改进方法[J].电力工程技术,2018,37(6):156-160

复制
分享
文章指标
  • 点击次数:1900
  • 下载次数: 2193
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 收稿日期:2018-07-09
  • 最后修改日期:2018-08-14
  • 录用日期:2018-04-17
  • 在线发布日期: 2018-11-28
  • 出版日期: 2018-11-28
文章二维码