In Xizhe HVDC project the PROFIBUS DP communication false alarm occurs frequently,which is triggered by the detection of the heartbeat signal.It is found that the PROFIBUS DP communication system is a multi-link asynchronous system.The time window of the heartbeat signal is changed by the data transfer in the multi-link asynchronous system,and the continuous multi-frame has the same heartbeat signal,which causes the false alarm of PROFIBUS DP.In this paper,the characteristics of heartbeat signal transmission in multi-link asynchronous system are analyzed in detail.The research method can be applied to similar structure commnunication systems.
参考文献
相似文献
引证文献
引用本文
曾丽丽.溪浙特高压直流工程PROFIBUS DP通信告警分析[J].电力工程技术,2017,36(2):38-42,98. ZENG Lili. Analysis of PROFIBUS DP Alarm in Xizhe HVDC Project[J]. Electric Power Engineering Technology,2017,36(2):38-42,98.